INVESTIGATION OF INFLUENCE OF FACTORS ON FIRE RESISTANCE OF PARTITIONS MADE OF SANDWICH PANELS

Authors

  • Y. Danchenko National Academy of the National Guard of Ukraine
  • Y. Kachkar Cherkassy institute of Fire Safety named after Сhernobyl Heroes of National University of Civil Protection of Ukraine
  • N. Rashkevich National University of Civil Defence of Ukraine

DOI:

https://doi.org/10.33042/2522-1809-2023-1-175-145-150

Keywords:

fire-resistance, methodological support, parameters, modeling

Abstract

The authors describe the results of studies of thermal processes in partitions made of sandwich panels under one-sided influence of fire.

Analysis of the thermal state of multilayer partitions with mineral wool plates and development of recommendations for the design of buildings from such structures is possible using the simulation of thermal processes that occur during fire exposure to the studied samples. There is a certain number of models of the thermal state of multilayer partitions with mineral wool plates of different levels of complexity and purpose. However, in these models there are parameters that are individual for each partition and are known with insufficient accuracy.

The authors provided an improved mathematical model of heat conduction in partitions, the difference of which is the application of heat transfer coefficients from the unheated surface of the partition in boundary conditions. A comparison of the fire resistance limits for a partition made of a sandwich panel indicates a strong influence of the accuracy of setting the heat transfer coefficient on the dependence of the thickness of the partition on the fire resistance limit. The accuracy of the task of the heat transfer coefficient on the dependence of the thickness of the partition on the fire resistance limit was scientifically substantiated, which showed a strong influence of the boundary condition describing the processes of heat transfer on the surface of the partition, which is not heated, on the accuracy of determining the limits of fire resistance of the structure under study. The influence of the accuracy of the assignment of the coefficient of heat transfer from the object to the environment on the fire resistance of the investigated building structures, which during the test are subject to both natural (mobility) of air and forced blowing, as, for example, during tests of air ducts with fire protection, must be taken into account convectively radiation heat exchange, which will allow to obtain the most accurate result regarding the determination of their fire resistance characteristics.

Author Biographies

Y. Danchenko, National Academy of the National Guard of Ukraine

Doctor of technical sciences, professor, professor of the department of fundamental disciplines

Y. Kachkar, Cherkassy institute of Fire Safety named after Сhernobyl Heroes of National University of Civil Protection of Ukraine

PhD, Associate Professor, Associate Professor of the Department of Organization of Civil Protection Measures

N. Rashkevich, National University of Civil Defence of Ukraine

PhD, Lecturer of the Department of fire prevention in settlements

References

Veselivskyi, R.B., Yakovchuk, R.S., Vasylenko, O.O., Semenyuk, P.V. (2015). Experimental study of fire resistance of enclosing structures with plasterboard plates. Fire safety: coll. of science works, (26), 19–26.

Polovko, A.P. Veselivskyi, R.B., Vasylenko, O.O., Husk, Yu.E. (2011). Experimental study of fire resistance of multi-layer enclosing structures. Fire safety: coll. of science works, (19), 118–123.

Sherstinyuk, N.L. Loik, V.B. (2014). Rationale for the effectiveness of using vermiculite silicate boards to increase the fire resistance of sandwich panels. Fire safety: coll. of science works, (25), 96–102.

Novak, S.V., Drizhd, V.L., Dobrostan, O.V. (2021). Evaluation of fire-resistant properties of coatings and facings for steel structures. Scientific Bulletin: Civil defense and fire safety, 2(12), 43–53.

Pozdeev, S.V. [etc.] (2011). Metrological features of fire tests of reinforced concrete building structures for fire resistance of structures. Fire safety: theory and practice: coll. of science works, (8), 73–79.

Krukovsky, P.G., Tadlya, O.Yu. (2007). Identifiability of the parameters of the thermal regime model of a typical two-room apartment structure. Industrial Heat Engin., (5), 54–63.

Kachkar, E.V. (2010). Identifiability of the parameters of the thermal state model of sandwich panels with mineral wool boards. Problems of Fire Safety, (27), 70–76.

Bogoslovsky, V.N. (1970). Building thermophysics (thermophysical fundamentals of heating, ventilation and air conditioning), 376.

EN 1992-1-1:2004 Eurocode 2: Design of concrete structures – Part 1-1: General rules and rules for buildings.

Published

2023-04-03

How to Cite

Danchenko, Y., Kachkar, Y., & Rashkevich, N. (2023). INVESTIGATION OF INFLUENCE OF FACTORS ON FIRE RESISTANCE OF PARTITIONS MADE OF SANDWICH PANELS. Municipal Economy of Cities, 1(175), 145–150. https://doi.org/10.33042/2522-1809-2023-1-175-145-150